Z-WALL 2 Story1Allowable Load2Table #33

Verticals= C 3 x 4.1
Diagonals = 2" x 2" x 14 Ga.

 
 
Plate Height Designation
Width x Height
Earthquake4
Maximum Load(lbs)
Wind5
Maximum Load lbs
Story Drift6
(inches)
W (Rf D+Flr D+Flr L) 0k/ft 1k/ft 2k/ft 0k/ft 1k/ft 2k/ft  
2ndStory 8'1" 17.5" X 85" 9.83 8.83 8.00 7.02 6.30 5.71 .382
1st Story 8'1" 17.5" X 92.25"   .337
 
2nd Story 8'1" 23.5" X 85" 11.40 10.00 9.33 8.14 7.14 6.66 .330
1st Story 8'1" 23.5" X 92.25"   .289
 
2nd Story 8'1" 29.5" X 85" 13.20 12.00 10.60 9.43 8.57 7.57 .299
1stStory 8'1" 29.5" X 92.25"   .274

W (Rf D+Flr D+Flr L) 0k/ft 1k/ft 2k/ft 0k/ft 1k/ft 2k/ft  
2ndStory 8'1" 17.5" X 97" 9.16 8.33 7.50 6.87 6.25 5.63 .402
1stStory 9'1" 17.5"X104.25"   .377
2ndStory 8'1" 23.5"X 97" 10.80 9.60 8.80 8.10 7.20 6.60 .337
1st Story 9'1" 23.5" X 104.25"   .341
2ndStory 8'1" 29.5" X 97" 12.60 11.20 9.90 9.23   7.43 .310
1st Story 9'1" 29.5" X 104.25"   .319

W (Rf D+Flr D+Flr L) 0 k/ft 1 k/ft 2 k/ft 0 k/ft 1 k/ft 2 k/ft  
2nd Story 9' 1" 17.5"X 97" 9.00 8.00 7.30 6.75 6.00 5.48 .464
1st Story 9'1" 17.5" X 104.25"   .403
2ndStory 9'1" 23.5" X 97" 10.60 9.40 8.60 7.95 7.05 6.45 .402
1st Story 9'1" 23.5" X 104.25"   .338
 
2nd Story 9'1" 29.5" X 97" 12.00 10.80 9.60 9.00 8.00 7.20 .359
1st Story 9'1" 29.5" X 104.25"   .311

W (Rf D+Flr D+Flr L) 0 k/ft 1 k/ft 2 k/ft 0 k/ft 1 k/ft 2 k/ft  
2nd Story 9' 1" 17.5" X 97" 8.16 7.5 7.16 5.83 5.36 5.11 .442
1st Story 10'1" 17.5" X 116.25"   .460
 
2nd Story 9' 1" 23.5" X 97" 9.60 8.70 8.40 6.85 6.21 6.00 .393
1st Story 10'1" 23.5" X 116.25"   .382
 
2nd Story 9'1" 29.5" X 97" 11.00 10.00 9.60 7.86 7.14 6.86 .353
1st Story 10'1" 29.5" X 116.25"   .345
 

1 The Roof Header is assumed to be a 4x8, (at maximum Earthquake loading a 4x10 is required) and the Floor Beam is assumed to be a
  3.5"x11.875" Parallam.

2 The distribution of Lateral Load can vary as long as the Overturning Moments and the Story Shears resulting from the figures shown in
   the Table are not exceeded.

3 W= indicates the Total (Roof DL+Floor DL+Floor LL) Uniformly Distributed Service Load in kips per lin. ft. to the structure

4 This column indicates the Total Earthquake Load (Base Shear) as defined in 1997 UBC, Sec. 1630.1.1, distributed as follows: 60% to
   the Roof Diaphragm and 40% to the Floor Diaphragm.

5 This column indicates the Total Wind Load  distributed as follows: 60% to the Roof Diaphragm and 40% to the Floor Diaphragm. The
   Maximum Wind Loads have been set at E/1.4.

6 The Story Drift is calculated using D+L+E/1.4 and D+L+W Load Factors.

"All of the appropriate 1997 UBC Load Combination factors have been included, therefore enter these tables with E, not with E/1.4.